NEWPWR NPEXA-C511 Digital input isolated barrier
Digital input isolated barrier, it converts switch or proximity detector signals (dry contact or NAMUR) from a hazardous area into relay signals to a safe area by isolation. The normal output sate and line fault detection function can be set with the DIP switch. The input, output, and power supply are galvanically isolated from each other.
Supply
Power supply
18 ~ 60 V DC
Input
Input signal
Dry contact or NAMUR
Output
Output signal
Relay contact
Load capacity
250VAC/2A, 30VDC/2A
General parameters
Switching trigger point
Input signal > 2.1mA, signal “1”, the yellow LED is always bright; Input signal < 1.2mΑ, signal “0”, the yellow LED goes out
Relay mechanical life
> 100000 switching cycles
Switch frequency
< 10 Hz
DIP switch settings
S1→a:output1 normal mode;S1→b:inverted mode;S2→a:LFD on;S2→b:LFD off
Response time
< 20 ms
Power dissipation
1 W
EMC data
Electromagnetic compatibility
IEC 61326-3-1
Dielectric strength
≥ 3000V AC (intrinsically safe side / non-intrinsically safe side); ≥ 1500V AC (Power supply /non-intrinsically safe side)
Insulation resistance
≥ 100 MΩ (Input /Output/Power supply)
Operating conditions
Operation temperature
-20 ℃ ~ +60 ℃
Storage temperature
-40 ℃ ~ +80 ℃
Suitable location
Mounting in safe area, and connected to the intrinsic safety apparatus in hazardous area zone 0, zone 1, zone 2, ⅡA, ⅡB, ⅡC, T4 ~ T6
State
LFD function
When input current ≤ 50μA, considers the input line breakdown, the output relay de-energized. If input current ≥ 6.5mA, considers the input circuit short-circuit, the output relay de-energized, the indicator red flashing
Mechanical specifications
Connection method
Screw connection
Dimension
12.8mm (W) × 110mm (H) × 117mm (D)