Honeywell RTU2020 is a modular Remote Terminal Unit (RTU) designed for process industries such as oil & gas, mining, etc. Its key features include low power consumption (typically only 1.8W), onboard 28 mixed I/O channels all with built-in HART protocol, and support for a wide operating temperature range of -40°C to 75°C.
Core Models and Component List
The RTU2020 uses a modular design. A complete system typically consists of the following components:
1. Core Controller
This is the "brain" of the system, responsible for logic execution and data processing. Some models also integrate I/O points.
Model Description / Key Parameters Typical Use
SC-UCMX01 (51307198-175) 28 mixed I/O points (8AI, 2AO, 10DI, 6DO, 2 pulse)
Dual-core 667MHz processor, supports HART protocol Standard main control unit
SC-UCMX02 Functionally similar to UCMX01, with possible slight configuration differences Standard main control unit
2. Expansion I/O Modules
Used to expand channel capacity when the controller's onboard I/O points are insufficient.
Model Description / Key Parameters Typical Use
SC-UCNN11 Expansion I/O module, requires IOTA backplane Increase I/O channels
SC-UMIX01 (51307550-175) 28-point mixed I/O module, HART-enabled, requires IOTA backplane Increase I/O channels
3. Backplanes and Accessories
Basic components used to mount modules and provide field wiring terminals.
Model Description / Key Parameters Typical Use
SC-TEPR01 IOTA backplane, right-side terminal block Mount CPM/IOM modules
SC-TEPL01 IOTA backplane, left-side terminal block Mount CPM/IOM modules
SP-EMD150/151/160 Power supply module, provides power to the RTU system System power supply
4. Software and Feature Options
These are software licenses or special function modules for advanced capabilities.
Model Description / Key Parameters Typical Use
SP-MCALC1 Flow calculation license Gas/liquid flow metering
SP-IHARTP HART protocol support license Enable HART communication
SP-IWIO01 Wireless I/O integration license Integrate ISA100 wireless devices
Hardware Architecture Description
Understanding the hardware architecture of the RTU2020 is very helpful for system selection and field maintenance. It mainly consists of the following parts:
CPM (Control Processor Module): The core controller such as the SC-UCMX01, which executes control logic and handles communication.
IOM (Input/Output Module): Expansion I/O modules such as the SC-UCNN11.
IOTA (Input/Output Terminal Assembly): The passive backplane (e.g., SC-TEPR01/TEPL01) used to mount CPM/IOM modules and provide field wiring terminals.
Selection and Application Recommendations
When selecting components for a project, consider the following points:
Small-scale applications: If the number of field I/O points is small, a single SC-UCMX01/02 with onboard I/O is usually sufficient.
Flow calculation required: If the application involves natural gas or petroleum metering, you need to purchase the SP-MCALC1 software license separately.
Larger scale: When more I/O points are needed, you can expand using I/O modules such as the SC-UCNN11, supporting up to 128 channels.