Megger MIT420/2 is an advanced CAT IV 600 V insulation and continuity tester from the MIT400 mk2 Series . Designed for both electrical and industrial testing applications, this multifunction instrument delivers professional-grade insulation testing capabilities in a rugged, weatherproof package .
The MIT420/2 features a variable test voltage range that allows any intermediate voltage from 10 V to 1000 V in 1 V steps, making it ideal for applications requiring specific test voltages not found in standard ranges.
Key Features
Feature Description
Insulation Testing Up to 1000 V and 200 GΩ range
Variable Test Voltage 10 V to 1000 V continuously adjustable (1 V steps)
Fixed Test Voltages 50 V, 100 V, 250 V, 500 V, 1000 V
Continuity Testing Single autoranging range from 0.01 Ω to 1.0 MΩ
Diagnostic Tests Polarization Index (PI) and Dielectric Absorption Ratio (DAR)
Stabilized Output Voltage maintained within -0% / +2% ±2 V of selected value
Live Circuit Detection Automatic detection and protection (>25 V triggers voltage measurement)
Data Storage Onboard memory for test results
Display Analogue arc with dual digital readout
IP Rating IP54 – Dust and water resistant
Safety Rating CAT IV 600 V / CAT III 1000 V
Technical Specifications
Insulation Testing
Parameter Specification
Test Voltages (Fixed) 50 V, 100 V, 250 V, 500 V, 1000 V
Variable Voltage Range 10 V to 1000 V (1 V steps)
Maximum Measurement 200 GΩ
Short Circuit Current 2 mA (+0% / -50% per EN 61557-2)
Test Current 1 mA at minimum pass values, maximum 2 mA
Open Circuit Voltage Accuracy -0% / +2% ±2 V
Measurement Accuracy ±2% ±2 digits
Insulation Resistance Ranges 10 GΩ / 20 GΩ / 50 GΩ / 100 GΩ / 200 GΩ
Continuity Testing
Parameter Specification
Measurement Range 0.01 Ω to 1.0 MΩ (autoranging)
Resolution 0.01 Ω
Open Circuit Voltage 5 V ±1 V
Test Current (0.01 Ω - 4 Ω) 200 mA (-0 mA / +20 mA)
Test Current (higher ranges) 20 mA
Lead Null Up to 9.00 Ω
Measurement Accuracy ±5% ±2 digits (0.01 Ω - 999 kΩ)
Voltage Measurement
Parameter Specification
DC Voltage Range 0 to 600 V
AC Voltage Range (TRMS) 10 mV to 600 V
AC Bandwidth 15 Hz to 400 Hz
DC Accuracy ±2% ±2 digits
AC Accuracy (sinusoidal) ±2% ±2 digits
Input Impedance 0.25 MΩ
Frequency Measurement
Parameter Specification
Measurement Range 15 Hz to 400 Hz
Accuracy ±0.5% ±1 digit
Capacitance Measurement
Parameter Specification
Measurement Range 0.1 nF to 10 μF
Accuracy ±5% ±2 digits
General Specifications
Parameter Specification
Display Analogue arc with dual digital display
Test Lock Function Yes (for continuous testing)
Leakage Current Display µA readout available during insulation test
Timer Control 60-second countdown timer
Data Storage >1000 test results
Power Supply 6 x 1.5 V AA (LR6) alkaline or 6 x 1.2 V NiMH rechargeable
Battery Life 3000 insulation tests (5 sec ON / 55 sec OFF @ 1000 V into 1 MΩ)
Auto Power Down Yes (configurable)