Megger MIT481 is a state-of-the-art insulation and continuity tester specifically designed for telecommunications and cable testing applications. Part of the MIT480 mk2 series, this instrument directly replaces the well-established BM80 product group, offering greater functionality with simplified operation . The MIT481 features an ergonomic, over-moulded design that fits comfortably in the hand and can be used equally well by left-handed or right-handed operators.
Key Features
Feature Description
Insulation Testing Up to 1000 V and 200 GΩ range
Continuity Testing Fast testing from 0.01 Ω to 1 MΩ
Test Voltages 50 V, 100 V, 250 V, 500 V, 1000 V
Diagnostic Tests Polarization Index (PI) & Dielectric Absorption Ratio (DAR)
Display Dual digital and analog arc display
Live Circuit Detection 75 V warning and protection
Data Storage Test result storage with recall capability
IP Rating IP54 – Weatherproof and dust resistant
Safety Rating CAT IV 600 V
Technical Specifications
Insulation Testing
Parameter Specification
Test Voltages 50 V, 100 V, 250 V, 500 V, 1000 V
Maximum Insulation Resistance 200 GΩ
Short Circuit Current 2 mA maximum
Live Circuit Warning 75 V
Terminal Voltage Accuracy Stabilized output maintained under load
Continuity Testing
Parameter Specification
Measurement Range 0.01 Ω to 1 MΩ
Test Current 205 mA @ 0.01 Ω → 9.99 Ω; 20 mA @ 10.0 Ω → 99.9 Ω
Resolution 0.01 Ω
Audible Indication Fast buzzer with selectable threshold
Voltage Measurement
Parameter Specification
AC/DC Voltage Range 600 V True RMS
Frequency Measurement 40 Hz to 400 Hz
Accuracy TRMS measurement for accurate readings on non-sinusoidal waveforms
Capacitance and Distance Measurement
Parameter Specification
Capacitance Range 0.1 nF to 10 μF
Distance by Capacitance Cable length estimation based on capacitance measurement
General Specifications
Parameter Specification
Display Digital with analog arc display
Data Storage Test results can be saved and recalled
Bluetooth Available on MIT485/2; MIT481 supports storage only
Power Supply 6 x AA alkaline or NiMH batteries
Battery Life 2200 insulation tests (5 seconds ON / 55 seconds OFF @ 1000 V into 1 MΩ)
Fuse Access Separate fuse access compartment