Megger MIT1015 is a 10 kV insulation resistance tester belonging to Megger's Essential product line within the MIT series. Designed for go/no-go testing applications, this instrument is ideal for technicians and engineers working in demanding field environments who require reliable high-voltage insulation testing without the need for onboard data storage or remote control capabilities .
The MIT1015 is part of Megger’s globally renowned family of 5 kV, 10 kV, and 15 kV insulation testers, known for rugged dependability, long service life, and accurate measurements . Common features across the range include a no-compromise approach to safety and an intuitive colour custom display with an unbeatable viewing angle, even in extreme environments .
Key Features
Feature Description
Maximum Test Voltage 10 kV
Maximum Resistance Measurement 20 TΩ
RE>Act™ Mode Enhanced accuracy and safety by monitoring reabsorption current
PI Predictor™ (PIp) Predicts Polarization Index in 3-5 minutes, reducing test time by up to 50%
Noise Rejection Up to 3 mA interference rejection
Safety Rating CAT IV 600 V to 3000 m altitude
Dual Power Supply Rapid-charge Li-ion battery or AC mains operation
Dual-Case Design Unique fire-retardant inner shell with rugged outer protection
IP Rating IP65 (lid closed), IP40 (lid open)
Operating Temperature -20°C to +50°C
Technical Specifications
Insulation Testing
Parameter Specification
Fixed Test Voltages 500 V, 1000 V, 2500 V, 5000 V, 10000 V
User-Defined Voltage 40 V to 1000 V in 10 V steps
Resistance Range 10 kΩ to 20 TΩ @ 10 kV
Resistance Accuracy ±5% up to 2 TΩ @ 10 kV; ±20% up to 20 TΩ @ 10 kV
Test Modes IR, IR(t), DAR, PI
Short Circuit / Charge Current 3 mA (default maximum)
Current Measurement Range 0.01 nA to 6 mA
Current Accuracy ±5% ±0.2 nA at all voltages
Capacitance Measurement
Parameter Specification
Capacitance Range 10 nF to 25 μF
Capacitance Accuracy ±10% ±5 nF
Capacitor Charge Time <5 s/μF at 3 mA to 10 kV
Capacitor Discharge Time <250 ms/μF to discharge from 10 kV to 50 V
Voltage Measurement
Parameter Specification
Voltmeter Range 30 V to 660 V AC or DC
Voltmeter Frequency 45 Hz to 65 Hz
Voltmeter Accuracy ±3%, ±3 V
AC Power Supply 90 to 264 V rms, 47 to 63 Hz, 100 VA
General Specifications
Parameter Specification
Battery Type 11.1 V, 5.2 Ah Li-ion (IEC 62133:2003 certified)
Battery Life 4.5 hours continuous testing at 10 kV with 100 MΩ load
Battery Charge Time 2.5 hours (deep discharge), 2 hours (normal)
Timer Range Up to 99 minutes 59 seconds
Guard Terminal Performance Guards out current IG ≥5000× IL at 100 GΩ / 5000 V
Dimensions (L × W × H) 315 × 285 × 181 mm
Weight 4.5 kg (instrument only)
Environmental & Safety
Parameter Specification
Operating Temperature -20°C to +50°C
Humidity 90% RH non-condensing at 40°C
Altitude Up to 3000 m
IP Rating IP65 (lid closed), IP40 (lid open)
Safety Rating CAT IV 600 V to 3000 m
Test Capabilities
The MIT1015 supports the following diagnostic test modes :
Test Mode Description
IR Basic insulation resistance measurement
IR(t) Insulation resistance with time recording
DAR Dielectric Absorption Ratio
PI Polarization Index
PI Predictor™ Predicts 10-minute PI value in 3-5 minutes
RE>Act™ Compensates for reabsorption current to prevent incorrect pass/fail results