Number of analog inputs:2
Total number of channels (module):2
Signal type:Current
Signal type (current):4 … 20 mADC
Sensor connection:2 x (2-wire)
Input filter:Low pass (1st order), fG = 5 kHz
Signal characteristics:Differential
Resolution [bit]:13Bit
Operating mode:Continuously sampling (default)
Input resistance (max.):270Ω
Data width:2 x 16-bit data; 2 x 8-bit control/status (optional)
Protective device:Non-linear limiting
Admissible continuous overload:30V
Crosstalk attenuation:80dB
Monotonicity without error code:yes
Measurement error (reference temperature):25°C
Measurement error, deviation (max.) from the upper-range value:0.05%
Measurement error over entire temperature range:≤ 0.4 %
Temperature error (max.) of the upper-range value:0.01%/K
Sampling duration:5μs
Sampling delay (channel/channel):1μs
Sampling delay (module):1ms
Sampling repetition time:1ms
Fire load:0.882MJ
Weight:56.5g
Ambient temperature (operation):0 … +55 °C
Ambient temperature (storage):-40 … +85 °C
WAGO 753-602 Power Supply
WAGO 753-550 analog output module
WAGO 753-530 digital output module
WAGO 753-517 relay output module
WAGO 753-492 analog input module
WAGO 753-467 analog input module
WAGO 753-430 digital input module