ABB DPT160-CB011 R32 3P transfer switch controller is a device for dual power switching. The following is its detailed introduction:
Basic parameters: "160" means the frame current is 160A, "R32" usually means the rated current is 32A, and "3P" means it is a three-pole switch, suitable for three-phase circuits, and can control three-phase live wires.
Control core: It uses a single-chip microcomputer as the control core, with simple hardware design, powerful functions, convenient expansion, and high reliability.
Protection function: It has short circuit and overload protection functions, and can also realize overvoltage, undervoltage, and phase loss automatic conversion and intelligent alarm functions, which can effectively ensure the safety of circuits and loads.
Working mode: It supports automatic investment and automatic recovery and automatic investment without automatic recovery. In the automatic investment and automatic recovery mode, the common power supply is powered by it when it is normal, and the common power supply is switched to the backup power supply when it fails, and it is automatically switched back after the common power supply is restored; in the automatic investment without automatic recovery mode, after the common power supply is restored to normal, the switch will not automatically return to the common power supply.
Operation mode: It can switch automatically with load, and can also switch manually through the handle in an emergency. There is an interlock between manual and automatic operation modes, and manual operation is not possible in the automatic state, which improves the safety of use.
Protection level and application category: The protection level is IP20, which can prevent the entry of solid foreign objects larger than 12mm, and is suitable for general indoor environments. The application category is AC-33B, which is suitable for controlling related circuits such as motor loads.
Time setting function: You can set the normal power return time (Tn), the backup power return time (Tr), and the normal or backup switching to the double split position time (Ts). Users can accurately set the power switching time according to actual needs.
Compliance with standards: Comply with relevant standards such as GB14048.11-2002 to ensure that product quality and performance meet industry specifications.