The Triconex 3806E is a high-performance communication module designed for Tricon v9, v10, and Tricon CX/MX safety systems, providing critical connectivity between the safety controller and external systems. Here's a detailed technical breakdown:
Triconex 3806E – Technical Specifications
1. Module Type & Function
Model: 3806E (Enhanced version of the 3800 series)
Primary Role: Ethernet Communication Module
Key Features:
Dual-redundant Ethernet ports (10/100Base-T) for high availability
TMR Bus Interface for internal Tricon communication
Supports Modbus TCP/IP for SCADA/DCS integration
OPC Server compatibility for advanced data exchange
2. Communication Protocols
Protocol Function
Modbus TCP/IP Primary protocol for external communications
Triconex TMR Bus Internal controller communication
ICCP (Optional) For power industry applications
3. Performance Specifications
Data Rate: 10/100 Mbps auto-negotiating
Latency: <5ms for critical safety messages
Max Connections: 32 simultaneous TCP/IP connections
Isolation: 1500V optical isolation for noise immunity
4. LED Status Indicators
LED Color Status Indication
PWR Green Module powered
OK Green Normal operation
ACT Yellow Network activity
LNK Green Ethernet link established
FLT Red Fault condition
5. Configuration & Programming
IP Configuration: Static or DHCP (not recommended for safety systems)
Port Assignment: Configurable TCP ports (default 502 for Modbus)
Firewall Rules: Configurable through TriStation software
6. Environmental & Certifications
Operating Temp: -40°C to +70°C
Certifications:
IEC 61508 SIL 3
ATEX/IECEx for hazardous areas
CE, UL, cUL
7. Typical Applications
Safety System Integration with DCS/SCADA
Cloud Connectivity for remote monitoring (with proper security)
Tricon-to-Tricon communication in large installations
Historian Data Collection for safety event analysis
8. Installation Requirements
Slot: Dedicated communication slot in Tricon chassis
Cabling: CAT5e or better, with proper grounding
Separation: Minimum 30cm from power cables
9. Troubleshooting Guide
Common Issues:
No Network Connection
Verify Ethernet cable integrity
Check switch port configuration (auto-negotiation)
Confirm IP address conflicts
Intermittent Communications
Check for EMI sources near cables
Verify network switch health
Test with direct connection to eliminate network issues
Module Not Recognized
Verify backplane connection
Check chassis power supply
Confirm firmware compatibility
10. Maintenance Best Practices
Annual: Firmware version review
Biannual: Port connection tests
Event-Based: Full diagnostic after network changes
11. Ordering Information
Base Module: 4000103-3806E (verify suffix for hardware revision)
Accessories:
9725-xxx termination kits
Fiber optic converters (if required)
12. Comparison to Similar Modules
Feature 3806E 3704A 4351B
Ethernet Ports 2 1 N/A
Modbus TCP Yes Yes No
TMR Bus Yes Yes Yes
Redundancy Dual-net Single N/A