The following is an analysis of the core technologies of the ABB REM615E_L medium-voltage protection relay:
Core Positioning
Model: REM615E_L
Series: ABB Relion® 615 Economy Line Protection Relay
Suffix Meaning:
E: Standard hardware platform
L: Cost-optimized or specific installation configuration
Key Features and Differences (VS REM615E_G)
Features REM615E_G REM615E_L
Core Protection: Distance protection + overcurrent/ground fault/ARC Basic overcurrent/ground fault protection (no distance protection)
Communication Interfaces: 2 x Ethernet + RS485 1 x Ethernet + RS485 (simplified interface)
I/O Capacity: High-density DI/DO Standard DI/DO (reduced scalability)
Approvals: Global (UL/CE/IEC) Regional (e.g., CE only)
Typical Applications: Complex power distribution/new energy Simple feeder/OEM integration
Note: For specific function reductions, please refer to the ABB manual (document library link).
Core functions retained
Basic protection
Three-stage overcurrent protection (phase/zero sequence)
Ground fault protection
Voltage/frequency protection
Optional automatic reclosing (ARC)
Measurement and monitoring
Current/voltage/power measurement
Event logging and fault alarm
Communication protocol
Supports IEC 61850 (Basic Edition)
Modbus RTU/TCP
Design optimization
Cost control
Removal of advanced algorithms such as distance protection
Reduced number of communication interfaces
Simplified installation
Fixed terminal block (modular expansion not supported)
DIN rail mounting only (no panel cutout option)
Environmental adaptability
Standard temperature range (-25°C to +70°C)
Typical Applications
Building Power Distribution: 10kV Incoming Line Protection for Buildings
Industrial OEM Equipment: Integration into Motor Control Cabinets
Simple Branch Feeder: Radial Networks Without Distance Protection
Retrofit Project: Replacement of Older Overcurrent Relays (Low-Cost Upgrade)