Here's a precise technical overview of the ABB REC615E_G feeder protection relay in engineering terms:
ABB REC615E_G
Relion® 615 Series | Standard Configuration Feeder Protection & Bay Controller
1. Core Specifications
Parameter Detail
Hardware Platform REC615E
Suffix "G" Standard hardware configuration (default I/O, measurement, comms)
Protection Class IEC 60255, IEEE C37.90
Order Code 1MRK 511 356-BEN (verify latest datasheet)
2. Key Protection Functions
Primary Protection:
4-zone distance protection (mho/quad characteristic)
Directional/non-directional overcurrent (50/51, 51N/67N)
Auto-reclosing (79): 1–3 shots (single/three-phase)
Backup Protection:
Breaker failure (50BF)
Thermal overload (49)
Under/overvoltage (27/59)
3. Control & Automation
Bay Control:
CB open/close commands
Disconnector/interlock logic (programmable via PCM600)
Automation Features:
GOOSE-based inter-tripping
Load shedding schemes
Sectionalizing automation
IEC 61850 process bus (Sampled Values support)
4. Hardware Configuration
Module Specification
Analog Inputs 12 current / 4 voltage (standard accuracy ±0.5%)
Digital I/O 16 DI / 10 DO (configurable)
Communication 2× Ethernet (RJ45) + 2× optical (ST) + RS485
HMI 128×64 graphical LCD + keypad + status LEDs
5. Communication Protocols
Standard Functionality
IEC 61850 Ed.2 (GOOSE, MMS, Sampled Values)
DNP3.0 TCP/IP & serial
IEC 60870-5-103 Legacy serial comms
Modbus TCP/RTU
6. Typical Applications
Distribution Feeders (11–33 kV): Overhead line/cable protection
Industrial Grids: Motor feeder protection, bus-tie control
Ring Main Units (RMUs): Fault isolation in urban networks
Renewable Integration: Solar/wind collector feeder protection
7. Differentiation from REC615E_H
Feature REC615E_G REC615E_H
CT Accuracy ±0.5% (Class 0.5) ±0.2% (High-precision HCTs)
Sampling Rate 32 samples/cycle 64 samples/cycle
Cost ~15% lower Premium pricing
Use Case General feeder protection Sensitive differential protection
Engineering Notes
Feeder Differential Limitation:
Supports 87L only via fiber-optic links (requires external comms module).
Fault Recording:
8 GB internal storage for COMTRADE files (128 events).
Cybersecurity:
IEC 62351-compliant encryption for GOOSE/MMS.
Configuration:
Requires ABB PCM600 (v2.11 or later) for logic programming.
Critical Documentation:
Technical Manual: 1MRK 511 356-BEN
IEC 61850 CID Files: ABB Relion Library 615 series
Certification: KEMA, UL, CE
When to Specify REC615E_G
Budget-conscious greenfield distribution projects
Retrofitting legacy relays (REB500 compatibility)
Applications where ±0.5% measurement suffices
Schemes not requiring feeder differential protection
For high-impedance fault detection or short-cable differential, upgrade to REC615E_H.