1. Core Identity
Series: Relion® 615
Hardware Platform: REC615E
Suffix "H": Denotes high-precision analog inputs (HCTs) for sensitive measurements.
Primary Role: Feeder/bay control + advanced protection for distribution networks.
2. Key Functions
Category Functions
Protection - Distance protection (Zones 1–4)
- Directional/non-directional overcurrent (50/51, 50N/51N)
- Earth fault protection (67N, 50G/51G)
- Autoreclosing (79)
- Breaker failure (50BF)
- Thermal overload (49)
Control - IEC 61850-compliant bay control (switchgear control, interlocking)
- Logic programmable via PCM600
Measurement - High-accuracy synchrophasors (PMU support, IEEE C37.118)
- Power quality monitoring (harmonics, flicker)
Automation - GOOSE-based inter-tripping
- Load shedding
- Sectionalizing schemes
3. "H" Variant Distinction
High Core CTs (HCTs):
±0.2% current measurement accuracy (vs. ±0.5% in standard "G" models).
Critical for schemes requiring precision:
Differential protection (87L) for short feeders/cables.
Sensitive directional earth fault detection.
Enhanced Sampling:
64 samples/cycle for detailed waveform analysis.
4. Technical Specifications
Parameter Specification
I/O Configuration - 24 digital inputs
- 16 programmable outputs
- 4 analog inputs (mA/V)
Communication - 2× Ethernet ports (IEC 61850-8-1 Ed.2, MMS/GOOSE/SV)
- 2× optical ports (ST connector)
- RS485 (Modbus RTU, IEC 60870-5-103)
Protocols IEC 61850, DNP3.0 TCP, Modbus TCP, IEC 60870-5-104
Standards IEC 60255, IEEE C37.90 (EMC), IEC 61000-4-4/4-5 (Surge/EFT immunity)
Ordering Code 1MRK 511 358-BEN (verify with datasheet)