1. Core Identity
Series: Relion® 615
Hardware Platform: RET615E
Suffix "G": Denotes standard hardware configuration (default I/O, communication, and measurement).
Key Focus: Integrated transformer protection + distance-based teleprotection.
2. Core Functions
Protection Description
Transformer Diff. High-speed differential protection (87T) with harmonic restraint.
Distance Protection Zones 1–6 backup for lines/feeders (<1 ms operating time).
Teleprotection Communication-assisted schemes (POTT, DCB, DTT) via fiber/IEC 61850 GOOSE.
Backup Protections Overcurrent (50/51), Earth Fault (50N/51N), Breaker Failure (50BF), Voltage/Frequency (27/59, 81), Thermal Overload (49).
3. Key Features
Hardware ("G" Specific):
Standard-precision analog inputs (CTs/VTs) – suitable for most grid applications.
Default I/O: Typically 16 digital inputs / 10 digital outputs (configurable).
Communication:
Dual Ethernet ports (IEC 61850 Ed.2, DNP3.0 TCP, Modbus TCP).
Optical ports (IEC 61850-9-2 LE Sampled Values, IEEE C37.94 teleprotection).
Serial ports (IEC 60870-5-103, Modbus RTU).
Local HMI: Graphical LCD, keypad, and LED indicators for status/diagnostics.
Software: Fully configurable via ABB PCM600 (protection logic, schemes, HMI).
4. Technical Specifications
Parameter RET615E_G
Standards IEC 60255, IEEE C37.90, IEC 61000-4 (EMC)
Operating Temp -40°C to +85°C
IEC 61850 Support GOOSE, MMS, Sampled Values (SV)
Measurement Standard accuracy: ±0.5% (current), ±0.2% (voltage)
Ordering Code Typically 1MRK 504 085-BEN (verify datasheet)
5. Typical Applications
Substations: Backup protection for transformers + outgoing lines.
Grid Automation: Teleprotection for transmission lines (≤245 kV).
Industrial Plants: Main protection for critical transformers.
Renewables: Step-up transformer protection in wind/solar farms.
6. Differentiation from Other Variants
Model Key Difference
RET615E_H High-precision CTs (HCTs) for critical measurements
RET615E_V Enhanced voltage measurement (e.g., for generator)
REQ615E_* No distance protection (pure transformer focus)
Summary
The ABB RET615E_G is a versatile protection relay combining transformer differential protection, distance-based backup, and teleprotection schemes. Its "G" suffix designates a standard hardware configuration suitable for most grid and industrial applications. While lacking the ultra-high precision of the "H" variant, it delivers robust performance with full IEC 61850 compliance and flexible I/O.