The Eaton HMCP30R3C (also labeled as Cutler-Hammer HMCP Series) is a 30A, 3-pole thermal-magnetic circuit breaker designed for motor circuit protection and short-circuit protection in industrial applications.
Key Specifications:
Series: HMCP (Heavy Molded Case Protector)
Manufacturer: Eaton / Cutler-Hammer
Ampere Rating: 30A
Poles: 3 (3P)
Voltage Rating:
480V AC (typical)
600V AC (check datasheet for exact rating)
Interrupting Capacity (AIC):
65kA @ 480V (high fault current withstand)
Trip Type: Thermal-Magnetic (combines overload + short-circuit protection)
Thermal Trip: Protects against sustained overcurrent (heating)
Magnetic Trip: Instantaneous response to short circuits
Mounting: Fixed or plug-in (depending on model)
Standards: UL 489, CSA, IEC (industrial-grade)
Differences Between HMCP30R3C & HMCP30R4C
Feature HMCP30R3C (3P) HMCP30R4C (4P, 3P+N)
Poles 3 (L1, L2, L3) 4 (L1, L2, L3 + Neutral)
Protection Thermal-Magnetic Magnetic-only (short-circuit only)
Common Use Motor protection, general power Motor circuits requiring neutral protection
Typical Applications:
✔ Motor Protection (often paired with an overload relay for full protection)
✔ Industrial Power Distribution (switchgear, panelboards)
✔ Short-Circuit Protection in high-fault environments
Replacement & Cross-Reference:
Direct Replacement: HMCP030R3C (same series, newer catalog number)
Eaton Equivalents:
Eaton FAZ-C30/3 (for similar magnetic-only protection)
Eaton GJL30 (thermal-magnetic alternative)
Check compatibility with panel type (e.g., Eaton C-Series, Pow-R-Line).