ABB 1SBL141501R8000 ABB - A9-22-00 220-230V 50Hz / 230-240V 60Hz
Description:
A9-22-00 220-230V 50Hz / 230-240V 60Hz Contactor
100% insured shipping: A guarantee for your purchases
Express delivery: Worldwide delivery by DHL express courier
The contactors can also be used for many other applications such lighting... The A... series 4-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 2 N.O. + 2 N.C. main poles, front and side-mounted add-on auxiliary contact blocks - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessories is available.
Description: A9-22-00 220-230V 50Hz / 230-240V 60Hz Contactor
Product ID: 1SBL141501R8000
Extended Product Type: 1SBL141501R8000
Product Net Weight: 0.340 kgA 9 4-pole contactors are mainly used for controlling non-inductive or slightly inductive loads (i.e. resistance furnaces...) and generally for controlling power circuits up to 690 V AC and 440 V DC.
Product Net Width: 44 mm
Product Net Height: 74 mm
Product Net Depth: 74 mm
Degree of Protection: acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Ambient Air Temperature: Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 C Near Contactor for Operation in Free Air (Uc) -40 ... +70 C Close to Contactor for Storage -60 ... +80 C
Standards: Devices complying with international standards IEC 947-1 / 947-4-1, and European standards EN 60 947-1 / 60 947-4-1. Electromagnetic compatibility (EMC) acc. to amendment A11 to IEC 947-1; EN 60 947-1 and amendment 2 to IEC 947-4-1
Rated Impulse Withstand Voltage (U<sub>imp</sub>): 8 kV
Rated Insulation Voltage (U<sub>i</sub>): acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 600 V
Terminal Type: Screw Terminals
Number of Auxiliary Contacts NO: 0
Number of Auxiliary Contacts NC: 0
Mechanical Durability: 10 million
Connecting Capacity Main Circuit: Flexible with Cable End 0.75 ... 2.5 mm Rigid Cable 1 ... 4 mm
GOST Certificate: GOST_POCCFRME77B07175
Maximum Operating Altitude Permissible: 3000 m
Rated Control Circuit Voltage (U<sub>c</sub>): 50 Hz 220 230 V 60 Hz 230 240 V
Climatic Withstand: acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Mechanical Switching Frequency: 3600 cycles per hour
Connecting Capacity Auxiliary Circuit: Flexible with Cable End 0.75 ... 2.5 mm Rigid Cable 1 ... 4 mm
Operate Time: Between Coil Energization and NO Contact Closing 10 ... 26 ms Between Coil De-energization and NO Contact Opening 4 ... 11 ms Between Coil De-energization and NC Contact Closing 9 ... 16 ms Between Coil Energization and NC Contact Opening 7 ... 21 ms
Country of Origin: Finland (FI)
Number of Main Contacts NO: 2
GL Certificate: DNV-GL_TAE00000TX
Number of Main Contacts NC: 2
Short-Circuit Protective Devices: gG Type Fuses 25 A
Maximum Breaking Capacity: cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A
Coil Consumption: Pull-in at Max. Rated Control Circuit Voltage 50 Hz 70 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 80 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 8 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 2 W Holding at Max. Rated Control Circuit Voltage 50 Hz 8 V·A Holding at Max. Rated Control Circuit Voltage 50 Hz 2 W Average Holding Value 50 / 60 Hz 8 V·A Average Holding Value 50 / 60 Hz 2 W Average Pull-in Value 50 Hz 74 V·A Average Pull-in Value 60 Hz 70 V·A
Coil Operating Limits: (acc. to IEC 60947-4-1) 0.85 ... 1.1 x Uc (at 55 C) C
Connecting terminals (delivered in open position) Main poles: M 3.5 (+,-) pozidriv 2 screw with cable clamp
Lead Time: 999 day(s)
EAN: 3471522033802
Criticality: No
Replacement Part ID: <a href='javascript:constructLinkToDetailPage("ABB.PARTS.FISER64409506", "", "ROOT","");'>64409506</a>
Technical Information: 220-230V50Hz
Minimum Order Quantity: 1 piece