Manufacturer : Yokogawa
Product No. : YTA610-FA1A4DD/A/SU25
Product Type : Temperature Transmitter
Output signal : F = Digital communication (FOUNDATION Fieldbus protocol)
A : Always A (Global)
Sensor input : 1 = Single
Housing code : A = Aluminum
Electrical connection : 4 = M20 female
Integral indicator : D = Digital indicator with Local Operating Switch
Mounting bracket : D = SUS304 stainless steel 2-inch vertical pipe mounting bracket
Lightning protector : A = Allowable current: Max. 6000A(8×20µs), repeating 1000A(8×20µs), 100 times
IECEx : SU25
Fieldbus:
[Intrinsically safe ia approval]
Applicable Standard: IEC 60079-0: 2017, IEC 60079-11: 2011
Certificate No. IECEx FMG 16.0014X
Ex ia IIC T4 Ga
Ex ic IIC T4 Gc
Ex ia [ia Da] IIIC T135°C Db
Ambient Temperature: –55 to +60°C for T4 (Ex ia)
Ambient Temperature: –30 to +60°C for IIIC (Ex ia)
–30 to +70°C (Ex ic)
Enclosure: IP66/IP67
Overvoltage category: I
Electrical parameters (Ex ia)
Supply/Output circuit: Terminals: +, –
FISCO field device or
Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10µF, Lo=3.9mH
Electrical parameters (Ex ic)
Supply/Output circuit: Terminals: +, –
FISCO field device or
Ui=32V, Ci=2.2nF, Li=0mH
Sensor circuit:Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10µF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Flameproof and Dust Ignition Proof Approval]
Applicable standard: IEC 60079-0:2011 IEC 60079-1:2014-06, IEC 60079-31:2013
Certificate: IECEx KEM 07.0044
Ex db IIC T6/T5 Gb, Ex tb IIIC T70°C/T90°C Db
Ambient Temperature for Gas Atmospheres: –40 to 75°C (–40 to 167°F) for T6,
–40 to 80°C (–40 to 176°F) for T5
Ambient Temperature for Dust Atmospheres: –30 to 65°C (–22 to 149°F) for T70°C,
–30 to 80°C (–22 to 176°F) for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female*1
Weight : 2.3 Kg
Shipping Weight : 4Kg