Model and Suffix Codes :
Model: YTA610 - Temperature Transmitter
Output signal: -J - 4 to 20 mA DC with digital communication HART 7 protocol
A: Always A
Sensor input: 1 - Single
Housing code: A - Aluminium
Electrical code: 4 - M20 female
Integral indicator: D - Digital indicator with Local Operating Switch
Mounting bracket: N - None
Option Codes:
KU2: ATEX
4-20 mA:
[Intrinsically safe approval]
Applicable Standard: EN 60079-0; 2012+A11:2013, EN 60079-11:2012
Certificate No. FM16ATEX0019X
II 1 G Ex ia IIC T5...T4 Ga
Ambient Temperature: -40 to 70°C for T4, -40 to 50°C for T5
Enclosure: IP66/IP67 in accordance with only IEC 60529
Entity Parameters:
Supply/Output circuit: Ui=30V, li=200mA, Pi=1.0W, Ci-22nF, Li=0mH
Sensor circuit: Uo=6V, Io=90mA, Po=135mW, Co=10µF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s., 1 min
[+, -, C, 1, 2, 3, 4, 5] to Earth terminal
[+, -, C] to [1, 2, 3, 4, 5]
[Flameproof and Dust Ignition Proof Approval]
Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014
Certificate: KEMA 07ATEX0130
II 2 G Ex db IIC T6/T5 Gb, II 2 D Ex IIIC T70°C/T90°C Db
Ambient Temperature for Gas Atmospheres: -40 to 75°C for T6, -40 to 80°C for T5
Ambient Temperature for Dust Atmospheres: -30 to 65°C for T70°C, -30 to 80°C for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female²
NOTE:
Applicable for Electrical Connection Code 2 and 4.
Estimated Lead Time: 8 - 10 Weeks
Shipping Weight: 3 Kg