The technical parameters of ACS580MV-07-0267A-110 can refer to the general parameters of ACS580MV series, as follows:
- **Power parameters**
- **Input voltage range**: 3.3kV to 13.8kV±10% (-25% when reducing power)
- **Output voltage range**: 3.3kV to 11kV
- **Power range**: varies according to different voltage levels, such as 2000kW at 3.3kV, 2500kW at 4.16kV, 3550kW at 6kV, 3500kW at 6.3kV, 4000kW at 6.6kV, 5600kW at 10kV, 6300kW at 10.5kV, and 6300kW at 11kV
- **Power supply frequency**: 50/60Hz±5%
- **Motor frequency**: 0 to 120Hz output, rated motor frequency up to 80Hz
- **Protection and environmental parameters**
- **Protection level**: Standard is IP21, optional IP42 cabinet protection level
- **Ambient temperature**: Standard is 0℃ to +40℃, no frost or condensation, derating is required when the temperature reaches +50℃
- **Altitude**: Standard is 2000 meters and below, derating is required when exceeding 2000 meters
- **Certification parameters**: CE certification, GOST-R certification
- **Safety parameters**: Standard emergency stop category 0, optional SIL3/PLE
- **EMC and harmonic parameters**
- **EMC**: Complies with IEC 61000-2-4 Category 2, IEC 61800-3 Category 4
- **Harmonic suppression**: Complies with IEC 61800-3, IEEE 519-1992
- **Control connection parameters**
- **Analog input**: 4
- **Analog output**: 2
- **Digital input**: 6 freely programmable, 6 predefined
- **Digital output**: 5 freely programmable, 4 predefined
- **Communication interface**: Ethernet connection for PC tools, through the USB interface of the control panel, it can also support various fieldbus interfaces such as Profibus DP, DeviceNet, EtherNet/IP, Modbus TCP/RTU, Profinet IO, EtherCAT, Powerlink, ControlNet, etc.