Welcome to CW Green Tech Limited
info@cwlyautomation.com 86-136 6712 1125
Home      Products Endress+Hauser 7F2C1H-AAGCCADDAADAASKA1 Proline Prowirl F 200 Vortex Flow Meter
Endress+Hauser 7F2C1H-AAGCCADDAADAASKA1 Proline Prowirl F 200 Vortex Flow Meter

Endress+Hauser 7F2C1H-AAGCCADDAADAASKA1 Proline Prowirl F 200 Vortex Flow Meter

  • Product Item : 7F2C1H-AAGCCADDAADAASKA1
  • Product Brand : Endress+Hauser
  • INQUIRY

Endress+Hauser 7F2C1H-AAGCCADDAADAASKA1 Proline Prowirl F 200 Vortex Flow Meter


Specs at a glance

Max. measurement error

Volume flow (liquid): ±0.75 %

Volume flow (steam, gas): ±1.00 %

Mass flow (saturated steam): ±1.7% (temperature compensated); ±1.5% (temperature/pressure compensated)

Mass flow (superheated steam, gas): ±1.5 (temperature/pressure compensated); ±1.7% (temperature compensated + external pressure compensation)

Mass flow (liquid): ±0.85%

Measuring range

Liquid: 0.1 to 1700 m³/h (0.061 to 1000 ft³/min)

depending on medium: water with 1 bar a, 20 °C (14.5 psi a, 68° F)

Steam, gas: 0.52 to 22000 m³/h (0.31 to 13000 ft³/min)

depending on medium: steam with 180 °C, 10 bar a (356 °F, 145 psi a); air with 25 °C, 4.4 bar a (77 °F, 63.8 psi a)

Medium temperature range

Standard: –40 to +260 °C (–40 to +500 °F)

High/low temperature (option): –200 to +400 °C (–328 to +752 °F)

Max. process pressure

PN 250, Class 1500, 40K