1-channel signal conditioner
Universal usage at different power supplies
Input for 2- or 3-wire sensors, NAMUR sensors or dry contacts
Input frequency 1 mHz ... 10 kHz
Current output 0/4 mA ... 20 mA
Relay contact and transistor output
Start-up override
Line fault detection (LFD)
Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511
Signal type:Digital Input
Safety Integrity Level (SIL):SIL 2
Connection:terminals 23, 24
Programming interface:programming socket
Connection side:field side
Open circuit voltage/short-circuit current:22 V / 40 mA
Input resistance:4.7 kΩ
Pulse duration:> 50 μs
Open circuit voltage/short-circuit current:18 V / 5 mA
Output III:electronic output, passive
Contact loading:40 V DC
Output IV:analog
Current range:0 ... 20 mA or 4 ... 20 mA
Open loop voltage:max. 24 V DC
Load:max. 650 Ω
Response delay:≤ 200 ms
Display elements:LEDs , display
Control elements:Control panel
Height:119 mm
Width: 40 mm
Depth: 115 mm
KFU8-VCR-1