Signal type:Power measurement
Input voltage (max.):Current Inputs: 18 VAC
Signal form:Any periodic signals (considering the threshold frequencies)
Resolution [bit]:16Bit
Data width:2 x 48-bit data; 2 x 24-bit control/status (optional)
Voltage path input resistance (typ.):1071kΩ
Current path input resistance (typ.):22 mΩ
Reference for measurement error:AC current/voltage
Measurement error (reference temperature):25°C
Measurement error, deviation (max.) from the upper-range value:0.5%
Measurement current (max.):1 A
Measurement cycle time:Adjustable measuring cycle time for Min_Max_Values
Frequency range with activated DC filter:10 … 2000 Hz
Frequency range with deactivated DC filter:0 … 2000 Hz
Frequency range (mains frequency):45 … 65 Hz
Limit frequency:7,2kHz
Current consumption (5 V system supply):100mA
Isolation:4 kV system/field
Rated impulse withstand voltage:4 kV
Color:light gray
Housing material:Polycarbonate; polyamide 6.6
Fire load:0,955MJ
Weight:48,5g