Isolation
250V ac between input, output and power supply terminals
Tested at 1500V rms minimum between safe and hazardous-area
terminals
Terminals
Accommodate conductors up to 4mm2 (12AWG)
Mounting
On 35mm DIN (top-hat) rail (to EN 50022 – 35 x 7.5; BS 5584;
35 x 27 x 7.3 DIN 46277) or any flat surface
Location of units
Safe area
Ambient temperature limits
–20 to +60°C continuous working
–40 to +80°C storage
The MTL3992 should be spaced 5mm apart from
other units
Humidity
5 to 95% RH
EMC compliance
See 'CE marking for MTL products'.
CONDITIONS OF USE
The conditions governing the use of MTL3000 Series interface units
are given in the relevant certificates and schedules, copies of which
are available from MTL.
ENCLOSURES AND ACCESSORIES
A range of enclosures is available, and provides IP65 protection for up to 4, 8, 16 or 36 units (see 'MTL2000 and 3000 Series enclosures and accessories'). Alternatively, units can be installed in users’ own racks or panels using the MTL700 Series accessories, which also provide full tagging and cable screen earthing facilities. Details of these arrangements are given in the 'MTL700 Series accessories
MTL3000
MTL3011
MTL3012
MTL3013
MTL3014
MTL3041
MTL3042
MTL3043
MTL3045
MTL3046B
MTL3052
MTL3054
MTL3058
MTL3059
MTL3071
MTL3072
MTL3073
MTL3081
MTL3099
MTL3992