The MTL3073 converts a low-level dc signal from a temperature sensor mounted in a hazardous area into a 4/20mA current for
driving a safe-area load. Software-selectable features include linearisation, ranging, monitoring, testing and tagging for eight
thermocouple types and 2-, 3-, and 4-wire RTDs. For THC inputs requiring cold-junction compensation, an integral CJC sensor is
provided within the module. Configuration is carried out via a PC using the PCL45 interface and PCS45 software
Number of channels:One
Input signal range:–75 to +75mV, or 0 to 400Ω
Input signal span:3 to 150mV, or 10 to 400Ω
RTD excitation current:200µA nominal
Cold junction compensation:Automatic or selectable
Cold junction compensation error:≤1.0°C
Common mode rejection:120dB for 240V at 50Hz or 60Hz
Series mode rejection:40dB for 50Hz or 60Hz
Safety drive on sensor burnout:Upscale, downscale, or off
Weight:170g
MTL3000
MTL3011
MTL3012
MTL3013
MTL3014
MTL3041
MTL3042
MTL3043
MTL3045
MTL3046B
MTL3052
MTL3054
MTL3071
MTL3072
MTL3073
MTL3081
MTL3099