Input voltage range:1 x 90 … 264 VAC
Nominal mains frequency range:50 … 60 Hz
Inrush current:≤ 11 A (after 1 ms)
Power factor correction (PFC):Active
Mains failure hold-up time:≥ 25 ms (230 VAC)
Nominal output voltage Uo nom:24 VDC (SELV)
Output voltage range:24 … 28 VDC (adjustable)
Default setting:DC 24 V
Nominal output current Io nom:10 A (24 VDC)
Nominal output power:240W
Deviation:≤ 1 %
Residual ripple:≤ 70 mV (peak-to-peak)
Power supply with TopBoost, PowerBoost and configurable overload behavior
Configurable digital signal input and output, optical status indication, function keys
Communication interface for configuration and monitoring
Optional connection to IO-Link, EtherNet/IPTM, Modbus TCP or Modbus RTU
Suitable for both parallel and series operation
Natural convection cooling when horizontally mounted
Pluggable connection technology
Electrically isolated output voltage (SELV/PELV) per EN 61010-2-201/UL 61010-2-201
Marker slot for WAGO marking cards (WMB) and WAGO marking strips
2787-2146/0000-0030