Here is the technical parameter introduction of Danfoss FC102P160T4E00H2XGX:
Power Parameters
Rated Power: The rated power of this drive is 160 kW, which is suitable for medium - to - high - power applications such as large - scale fans and pumps.
Voltage and Current: It is designed for a three - phase power supply with a rated voltage range of 380 - 480 V. The rated current is 315 A at 480 V, ensuring stable power output within the specified voltage range.
Control Technology
Control Principle: It adopts the advanced EC + intelligent VVC + control principle, which is suitable for permanent - magnet motors and synchronous reluctance motors, enabling precise speed and torque control.
Auto - tuning PID Controllers: It is equipped with 4 auto - tuning PID controllers. The drive's controller observes the response of the controlled system to the corrections it makes, and then the PID controllers self - learn, adjust parameters, and output control signals, allowing the system to quickly enter a stable and precise operation state.
Energy Optimization: The standard - equipped Automatic Energy Optimization (AEO) function can optimize the motor's magnetization state under all speed and load conditions, improving energy efficiency by 5 - 15% under non - full - load conditions.
Enclosure and Protection
Protection Level: The enclosure of the Danfoss FC102P160T4E00H2XGX has a protection level of IP55/NEMA 12, which provides reliable protection against dust, water splashes, and other external factors, making it suitable for use in harsh industrial environments.
Built - in Functions
Fire - control Mode: In the event of a fire, the drive enters the fire - control mode. It will ignore normal control signals, warnings, and alarms to ensure the continuous operation of the HVAC system, providing necessary ventilation and smoke extraction functions to help with emergency evacuation.
Dry - pump Detection: The drive can detect the dry - running condition of the pump by monitoring relevant parameters such as pressure and flow. When a dry - pump situation is detected, the drive will take appropriate measures to prevent damage to the pump, thereby prolonging the service life of the pump.
Constant - torque Function: This drive can provide constant - torque output, which is useful in applications where a stable torque is required, such as in conveyor systems, cranes, and some industrial pumping applications.
Flow Compensation: By integrating with external sensors installed near the outlet of fans or pumps, the drive can perform flow compensation. This function optimizes the flow rate according to the actual demand, resulting in energy savings and reduced installation costs.
Sleep Mode: The drive can automatically detect low - flow or no - flow conditions in the system. When such conditions are detected, it will increase the system pressure for a short period and then enter a sleep state to save energy. When the pressure drops below the set lower limit, the drive will automatically restart to ensure the normal operation of the system.
Communication Capabilities
Standard Protocols: The standard built - in communication protocols include FC protocol and Modbus RTU, which allow for seamless communication and integration with other devices and systems in the industrial automation network, enabling remote monitoring and control of the drive.
Optional Protocols: Optionally, the drive can support a variety of other communication protocols, such as VLT® LonWorks MCA 108, VLT® BACnet/IP MCA 125, VLT® BACnet MCA 109, VLT® DeviceNet MCA 104, and VLT® PROFIBUS DP MCA 101, making it highly compatible with different building management systems and industrial control platforms.
I/O Interfaces
Digital Input: There are 6 programmable digital inputs, which can be configured as PNP or NPN logic with a voltage level of 0 - 24 VDC. Two of these digital inputs can also be used as digital outputs, providing flexible options for interfacing with other digital devices and controllers.
Analog Input: The drive is equipped with 2 analog inputs that can be configured to accept voltage or current signals. The voltage input range is 0 - 10 V (adjustable), and the current input range is 0/4 - 20 mA (adjustable), allowing for easy connection to various analog sensors and control devices.
Analog Output: There is 1 programmable analog output with a current range of 0/4 - 20 mA. This analog output can be used to provide control signals to other devices, such as adjusting the speed of a motor or the position of a valve.