Key Benefits at a Glance
1-channel isolated barrier
24 V DC supply (bus powered)
Dry contact or NAMUR input
Usable as signal splitter (1 input and 2 outputs)
2 passive transistor outputs
Fault transistor output
Line fault detection (LFD)
Reversible mode of operation
Up to SIL 2 (SC 3) acc. to IEC/EN 61508
Signal type:Digital Input
Ripple:≤ 10 %
Power dissipation:≤ 500 mW
Power consumption:≤ 600 mW
Switching point/switching hysteresis:1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection:breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Pulse/Pause ratio:min. 100 µs / min. 100 µs
Response time:≤ 200 µs
Switching frequency:≤ 5 kHz
Mass:approx. 90 g
Dimensions:12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Mounting:on termination board
Pepperl+Fuchs HiC2841
Pepperl+Fuchs HiC2883
Pepperl+Fuchs HiD2024
Pepperl+Fuchs HiD2038Y