The following is the parameter introduction of Schneider ATV930D250N4 inverter:
Basic specifications
Applicable motor power:
Standard load (variable torque): 250kW
Heavy load (constant torque): 200kW
Power supply specifications:
Voltage range: 3-phase 380 - 480V (±15%)
Frequency: 50/60Hz (±5%)
Protection level: IP21 (needs to be installed in the control cabinet)
Cooling method: forced air cooling
Performance parameters
Output current:
Standard load: 500A (380V) / 435A (480V)
Heavy load: 400A (380V) / 350A (480V)
Overload capacity:
Standard load: 110% for 60 seconds, 150% for 2 seconds
Heavy load: 150% for 60 seconds, 180% for 2 seconds
Output frequency range: 0.1 - 599Hz
Speed regulation accuracy:
Open loop: ±0.5% (maximum frequency)
Closed loop: ±0.01% (maximum frequency, encoder required)
Input/output interface
Digital input: 10 programmable inputs (DI1 - DI10), support 24V DC.
Analog input: 3 (AI1/2/3), support 0 - 10V or 4 - 20mA.
Analog output: 2 (AO1/2), 0 - 10V or 4 - 20mA, can output parameters such as frequency and current.
Relay output: 3 (RO1 - RO3), 250V AC/3A, for alarm or status indication.
Communication interface:
Standard Modbus RTU (RS485), Modbus TCP (Ethernet).
Optional expansion cards such as Profibus DP, DeviceNet, Ethernet/IP, etc.