The following is a detailed parameter introduction of Schneider ATV930P75N4 inverter, which belongs to the pump-specific inverter in the ATV930 series and is optimized for pump loads:
1. Basic specifications
Model: ATV930P75N4
Applicable motor power:
Standard load (variable torque): 75kW
Heavy load (constant torque): 55kW
Power supply specifications:
Voltage range: 3-phase 380 - 480V (±15%)
Frequency: 50/60Hz (±5%)
Protection level: IP21 (needs to be installed in the control cabinet)
Cooling method: forced air cooling
2. Performance parameters
Output current:
Standard load: 156A (380V) / 136A (480V)
Heavy load: 134A (380V) / 118A (480V)
Overload capacity:
Standard load: 110% for 60 seconds, 150% for 2 sec
Heavy load: 150% for 60 seconds, 180% for 2 seconds
Output frequency range: 0.1 - 599Hz
Speed regulation accuracy:
Open loop: ±0.5% (maximum frequency)
Closed loop: ±0.01% (maximum frequency, encoder required)
3. Special functions for pumps
PID control: Built-in PID regulator, supports closed-loop control of pressure, flow, liquid level, etc., and can achieve constant pressure water supply.
Multi-pump control: Supports cyclic soft start and master-slave control of 1-4 pumps to achieve intelligent switching of pump groups.
Sleep/wake-up function: Automatically sleep when water consumption is lower than the set value, and automatically wake up when demand is restored.
Anti-dry-run protection: Monitor the liquid level to prevent the pump from idling and damage.
Pump cleaning mode: Automatically start and stop regularly to prevent scaling of the pump body.
Smooth acceleration and deceleration: Optimized S-curve acceleration and deceleration to reduce water hammer effect.
4. Input/output interface
Digital input: 8 programmable inputs (DI1 - DI8), support 24V DC.
Analog input: 3 (AI1/2/3), support 0 - 10V or 4 - 20mA, can be configured as PID given or feedback.
Analog output: 2 (AO1/2), 0 - 10V or 4 - 20mA, can output parameters such as frequency and current.
Relay output: 3 (RO1 - RO3), 250V AC/3A, for alarm or status indication.
Communication interface:
Modbus RTU (RS485) and Modbus TCP (Ethernet) are standard.
Profibus DP, DeviceNet, Ethernet/IP and other expansion cards are optional.
5. Safety and protection functions
Safe torque off (STO): meets SIL3/PLe safety level and is implemented through safety input module.
Overload protection: thermal overload relay (electronic thermal protection).
Short circuit protection: built-in fast fuse.
Undervoltage/overvoltage protection: automatic detection and protection.
Ground fault protection: monitor ground current to prevent leakage.
Motor protection: supports PTC thermistor input to prevent motor overheating.
6. Physical characteristics
Dimensions (H×W×D): 922mm × 290mm × 325.5mm
Weight: 59.5kg
Installation: Wall-mounted
Ambient temperature: -15℃ to + 50℃ (derating is required if the temperature exceeds 40℃)
Relative humidity: 95% (no condensation)
Altitude: ≤1000m (derating is required if the temperature exceeds 40℃)
7. Model naming analysis
ATV930: Altivar Process series inverter
P: Pump Application
75: Suitable for 75kW motor (standard load)
N4: 3-phase 400V power supply specification
8. Typical application scenarios
Constant pressure water supply system: high-rise building water supply, industrial circulating water system.
Sewage treatment: sewage lifting pump, aerator control.
Air conditioning chilled water/cooling water system: energy-saving speed control.
Agricultural irrigation: automatic adjustment of pump speed according to water consumption.