Here's a detailed technical breakdown of the Schneider Electric LX1FH6002 TeSys F Contactor:
Key Specifications
Parameter Value
Series TeSys F Heavy-Duty (LX1F)
Rated Current (Ie) 600A (AC-3, 400V)
Poles 3P (3-pole)
Coil Voltage 24V DC (suffix "2")
Utilization Category AC-3 (motor control), AC-1, AC-4
Mounting Screw mounting (fixed frame)
Electrical Life ≈ 500,000 ops (AC-3)
Mechanical Life ≈ 2 million ops
Model Decoding: LX1FH6002
LX1F: Heavy-duty TeSys F contactor variant (robust construction for extreme loads).
H600: 600A rated operational current (Ie) at 400V AC (AC-3 duty).
2: Control coil voltage:
24V DC (common for PLC/control circuit compatibility).
*Note: Suffix "2" = DC coil; verify local voltage standards.*
Design & Key Features
Heavy-Duty Construction
Reinforced contacts & arc chutes for high-breaking capacity (IEC 60947-4-1).
Withstands inrush currents up to 12×Ie (e.g., 7,200A transient).
Integrated Mechanical Interlock
Built-in interlock slot (e.g., for FV2 kit) to prevent simultaneous closing in reversing applications.
DC Coil Advantages
Low power consumption, no hum noise, compatible with battery-backed systems.
Accessory-Ready
Supports:
Auxiliary contacts (LADN, LA series).
Pneumatic timers (PF/PFE).
Arc shields (FV-SHIELD).
Typical Applications
Heavy Industrial Motors:
600A = Controls ~300kW motors (400V AC).
Examples: Crushers, large compressors, shipyard cranes.
Frequent Switching: AC-4 duty (e.g., reversing/stalling motors).
DC Control Systems: Plants using 24V DC control voltage (e.g., process automation).