The ABB KORC 4L 185R/4 is a high-precision window-type (through-hole) current transformer designed for 12kV medium-voltage power systems. As part of ABB's renowned KORC series, this CT provides accurate current measurement and reliable protection for industrial switchgear applications, including ABB UniGear and other metal-enclosed switchgear panels.
This model is available under multiple ABB ordering codes, all referring to the same core specification:
1SCA022193R7830
1SCA022142R2670
CT4L185R/4 (Alternative Part Number)
All codes are fully interchangeable for ordering purposes.
EAN/GTIN: 4013614482113
Key Features & Benefits
Feature Benefit
Dual-core, dual-winding design Separate cores for measurement (Class 0.5) and protection (Class 5P10) ensure optimal performance for both functions without interference
Window-type (through-hole) construction Easy installation on cables or busbars without cutting primary conductors; ideal for retrofit and new panel builds
185A primary / 4A secondary ratio Standardized 4A secondary output compatible with most protection relays and metering devices
ABB UMC100 compatibility Specifically designed to work with ABB UMC100 and UMC100-FBP universal motor controllers
Compact footprint Fits seamlessly into ABB and third-party switchgear compartments
IEC compliance Meets IEC/EN 60947-1 and IEC/EN 60947-4-1 standards, ensuring global acceptance and reliability
ABB original quality Backed by ABB's global manufacturing and technical support network
Country of Origin Manufactured in India
Technical Specifications
Parameter Value
Brand ABB
Series KORC 4L
Type Window-type / Through-type Current Transformer
Rated Primary Current (Ipr) 185 A
Rated Secondary Current (Isr) 4 A
Turns Ratio 185:4
Core 1 – Measurement Winding
Parameter Value
Accuracy Class 0.5
Rated Burden 15 VA
Core 2 – Protection Winding
Parameter Value
Accuracy Class 5P10
Rated Burden 15 VA
Accuracy Limit Factor (ALF) 10
Accuracy Limit Current 1850 A (10 × Ipr)
General Specifications
Parameter Value
Frequency 50/60 Hz
Rated Insulation Level 12 kV (suitable for 12kV systems)
Power Frequency Withstand Voltage 28 kV / 1 min
Impulse Withstand Voltage 60 kV
Window Diameter Approx. 70–80 mm (for cable/busbar passage)
Standards IEC 61869-1, IEC 61869-2, IEC/EN 60947-1, IEC/EN 60947-4-1
Dimensions & Connection
Parameter Value
Product Net Width 192 mm
Product Net Height 98 mm
Product Net Depth / Length 43 mm
Product Net Weight 1.55 kg
Connecting Capacity 1x 1.5-6 mm²
Terminal Type Screw Terminals
Wire Stripping Length 7 mm
Model Number Decoding
Code Meaning
KORC ABB current transformer series designation
4L Series design framework; indicates dual-core configuration (measurement + protection)
185 Rated primary current: 185 Amperes
R Ring-type / window-type construction
/4 Rated secondary current: 4 Amperes
1SCA022193R7830 ABB ordering code (primary ordering number)
1SCA022142R2670 ABB ordering code (alternative number)
CT4L185R/4 Short-form ordering designation