Welcome to CW Green Tech Limited
info@cwlyautomation.com 86-136 6712 1125
Home      Products NOTIFIER JKM-FCM-1C NFS2-3030 series fire alarm control panels
NOTIFIER JKM-FCM-1C NFS2-3030 series fire alarm control panels

NOTIFIER JKM-FCM-1C NFS2-3030 series fire alarm control panels

  • Product Item : JKM-FCM-1C
  • Product Brand : Other
  • INQUIRY

The NOTIFIER JKM-FCM-1C is an output module designed for intelligent two-wire systems. Here is a detailed introduction:

Features

Easy Installation and Maintenance: It is equipped with SEMS-type screw terminals, which make installation and maintenance convenient.

Reliable Communication: It adopts noise - filtering technology to ensure reliable communication.

Bus - Powered: It is powered by the loop bus, with a working voltage of 15-28VDC.

Easy Address Coding: It has a decimal address setting, which is easy to code. The address range is 0 - 159.

Dual-Color LED Indicator: It is equipped with a dual - color and dual - light - emitting diode. The LED blinks green during patrol and turns red when an alarm occurs.

Technical Specifications

Power Supply: The normal working voltage is 15-32VDC. The static current is 200μA at 24VDC (LED flashing), and the maximum current is 5.1mA at 24VDC (LED on).

Output Characteristics: The maximum output loop line loss is 4VDC. The external power supply voltage (between terminals 10 and 11) is up to 24VDC (DC output) and 70.7VRMS, 50W (audio output). The maximum DC output current is 3A (Class B) and 2A (Class A).

Environmental Parameters: The working temperature range is - 10℃ - 55℃ (GB) or 0℃ - 49℃ (UL). The working humidity is 10% - 95% (GB) or 10% - 93% (UL) relative humidity, non - condensing.

Dimensions and Weight: The dimensions are 118mm (length) × 106mm (width) × 34mm (thickness), and the weight is 150 grams.

This module can be used to switch DC or audio signals (up to 80VRMS) and monitor whether the load line is normal, open - circuit, or short - circuit, feeding back its status to the controller. In addition, it provides two sets of spare terminals for fault - tolerant design and has an LED indicator controlled by the controller. It is suitable for use with NOTIFIER NFS2 - 3030 series mainframes and is widely used in fire alarm systems to realize the control and status monitoring of external equipment such as horns, strobes, and speakers.