The NOTIFIER N-LCD-100-A/128 is a specific model of fire display panel in the NOTIFIER fire alarm system. Here is a detailed introduction:
General Characteristics
It is a backlit floor display panel capable of showing 32 Chinese characters. It is mainly used to display fire alarm and fault information for corresponding floors or fire - resistant partitions, suitable for various building fire alarm projects.
Communication Capability
It can communicate over long distances with NFS2-3030 and NFS2-640 fire alarm controllers via the ACS interface of the EIA - 485 bus. Each controller can be connected to up to 32 N - LCD - 100 - A display panels, enabling centralized monitoring and management of fire alarm information in different areas.
Functions and Features
Functional Keys: The operation panel is equipped with four functional keys: self - test, mute, previous - check, and next - check. The self - test function allows the device to check its own working status; the mute function can turn off the local alarm sound; the previous - check and next - check functions are used to view relevant information such as fire alarm and fault records.
Status Indicators: There are two rows of LED status indicators below the liquid - crystal display, including fire alarm, mute, operation, fault, transmission, and feedback indicators. These indicators can visually display the working status of the device and the occurrence of relevant events.
Point Display: It can display 128 points of fire alarm and fault information, which can accurately locate the specific position of the alarm in the corresponding floor or fire - resistant partition, facilitating quick response and handling by relevant personnel.
Parameter Range: The voltage range is 20VDC - 28VDC, the static current (typical value) is 70mA at 24VDC, and the alarm current (typical value) is 150mA at 24VDC. The ambient temperature range is 0 - 50℃, and the relative humidity is 10% - 95%, non - condensing.