NOTIFIER's offers a variety of intelligent monitor modules for diverse applications. Monitor modules supervise a circuit of dry-contact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors. Monitor modules model numbers include the FMM-1, FMM-101, FZM-1 and FDM-1.
Specifications
Temperature Range: 32°F to 120°F (0°C to 49°C)
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 5.0 mA (LED on)
EOL Resistance: 47K Ohms
Average Operating Current: 375μA maximum (group poll); 350 μA (direct poll); 600 μA Max. (Communicating, IDC Shorted)
EOL resistance: 47K Ohms
Maximum Current Draw: 5.1 mA (LED on)
EOL Resistance: 3.9K Ohms
Maximum Current Draw: 6.4 mA (LED on)
EOL Resistance: 47K Ohm
Features & Benefits:
Built-in type identification automatically identifies this device as a monitor module to the control panel
SEMS screws with clamping plates for ease of wiring
Direct-dial entry of address: 01 – 159
LED indication for normal or off normal indication
FMM-1 Monitor Module
Class A supervised wiring to the monitored device
FMM-101 Mini Monitor Module
Class B supervised wiring to the monitored device
Smaller size fits inside devices or junction boxes
FZM-1 Zone Interface Monitor Module
Transmits the status of one zone of 2-wire detectors to the fire alarm control panel
Status conditions are reported as normal, open, or alarm
FDM-1 Dual Monitor Module
Monitors two separate Class B circuits