The NFS2-3030 series is an intelligent fire alarm control panel from Notifier's Onyx series, designed for medium - to large - scale facilities. Here is a detailed introduction:
Overview
Modular Design: It features a modular design that can be configured according to project requirements. It has 1 to 10 signaling line circuits (SLCs), supporting up to 3,180 intelligent addressable devices.
Display and Information: It is equipped with a large 640 - character liquid crystal display (LCD), which can present vital information to operators regarding fire situations, fire progressions, and evacuation details.
Features
Wireless Fire Protection: It supports wireless fire protection using Swift Smart wireless integrated fire technology.
Degraded Mode Operation: It has a built - in degraded mode. Even if the central processing unit (CPU) fails, the system can still issue a general alarm when a fire alarm condition exists.
Sensitivity Adjustment: It allows changing sensitivity by time of day and day of week through weekly occupancy schedules.
History Filter: It has advanced history filters that enable sorting by event, time, date, or address.
Networking Capability: It is network - capable. It can be networked with Notifier's i - Fire - Net and is Onyx Works-compatible, with a high - speed network supporting up to 200 nodes and a standard network supporting up to 103 nodes.
Logic Equations: It supports up to 1,000 powerful boolean logic equations.
Certifications: It has multiple certifications, including UL 864 (Fire), UL 1076, UL 257, ULC-S527-11, and is FM - approved.
Applications
The NFS2-3030 series is suitable for a wide range of applications, such as large - scale manufacturing plants, high - rise buildings, schools, universities, hospitals, and facilities with potentially explosive environments like oil, gas, and chemical production plants. It can also be used in scenarios that require gas detection, and when equipped with the appropriate seismic mounting kit, it is suitable for seismic applications. When using the marine - listed version with marine - listed compatible equipment, it can be applied to marine applications.
JTY-GD-FSP-851C: Intelligent photoelectric smoke detector.
JTW-BD-FST-851C: Intelligent temperature-sensing detector.
J-SAP-M-M500KC: Addressed manual alarm button.
J-XAP-M-M500HC: Addressed fire hydrant button.
JSM-FMM-1C: Input module.
JKM-FCM-1C: Output module.
KM-FZM-1C: Detector interface module.
ISO-X: Isolation module.
SSL24-6/8/10: Fire alarm bell.
P2475RLZ: Sound-and-light alarm.
P900: Sound-and-light alarm.
N-LCD-100-A/64: Floor display.
N-LCD-100-A/128: Floor display.
N-LCD-100-A/256: Floor display.
NCA-2: Network display controller.
NCA-2-SC: Network display controller CPU.
JTY-GD-2151EIS: Explosion-proof ordinary photoelectric smoke detector.
JTWB-BCD-5151EIS: Explosion-proof ordinary temperature-sensing detector.